Analog input module error definition table, Module errors – Rockwell Automation 1790D-NOV2/TNOV2 CompactBlock LDX Analog Modules User Manual

Page 59

Advertising
background image

Publication 1790-UM001A-EN-P - March 2002

Module Diagnostics and Troubleshooting 5-5

Analog Input Module Error
Definition Table

Analog input module errors are expressed on a channel bases in input
read word 4. The structure of the status data is shown below.

Word/Bit Descriptions

Module Errors

Table 5.4 lists possible errors that cause the analog input module
status bits to be set.

Table 5.3

Word

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

4

Not used

S3

S2

S1

S0

Word

Decimal Bit

Description

Read Word 4

Bits 00-03

Status bits for individual channels - Bit 00 corresponds to input
channel 0, bit 01 corresponds to input channel 1 and so on.
When set (1) indicates:

No field power

Open wire (4-20mA current input only)

Under range (4-20mA current input only)

Recoverable module fault (whole channel to be set)

Unrecoverable module fault (whole channel to be set)

Bits 04-15

Not used: Set to 0

Table 5.4
Status Bit Table 1790D-N4CO/-TN4CO, 1790D-N4VO/-TN4VO

Range
Setting

Underrange

In Range

Overrange

Open
Circuit

Short
Circuit

No Field
Power

4-20mA

<4mA
Set

Not set

>20mA
Not set

Set

Set

Set

0-20mA

<0mA
Not set

Not set

>20mA
Not set

Not set

Not set

Set

0-10V dc

<0V dc
Not set

Not set

>10V
Not set

Not set

Not set

Set