Rockwell Automation 1790D-NOV2/TNOV2 CompactBlock LDX Analog Modules User Manual
Page 26

Publication 1790-UM001A-EN-P - March 2002
2-10 Installation and Wiring
For example, for Belden 8761 two conductor, shielded cable:
Rc = 16
Ω
/1000 ft
Rs = 0 (ideal source)
As input source impedance (Rs) and/or resistance (dc) of the cable
(Rc) get larger, system accuracy decreases. If you determine that the
inaccuracy error is significant, implementing the following equation in
the control program can compensate for the added inaccuracy error
due to the impedance of the source and cable.
Table 2.2
Effect of Cable Length on Input Accuracy
Length of Cable (m)
dc resistance of the
cable, Rc (
Ω
)
Accuracy impact at the
input module
50
2.625
0.00105%
100
5.25
0.00210%
200
10.50
0.00420%
300
15.75
0.00630%
TIP
In a current loop system, source and cable
impedance do not impact system accuracy.
%
Ai
1
Vin
Vs
---------
–
100
×
=
Vs
Vin
Rs
2
Rc
×
(
)
Ri
+
+
[
]
Ri
-------------------------------------------------------
Ч
=