Specifications

DeviceNet Analog Base Terminal Block

The following table contains specifications that are common to all of
the blocks in this document. Individual base block specifications are
detailed after this table.

Environmental Specifications

Operating
Temperature

0 to 55°C (32 to 131°F)
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

Storage Temperature

-40 to 85°C (-40 to 185°F)
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal
Shock)

Relative Humidity

5-90% non-condensing
IEC 60068-2-30 (Test Db, Un-packaged Non-operating)

Operating Altitude

2000m

Vibration

IEC60068-2-6 (Test Fc, Operating):
2g @ 10-500Hz

Shock

Operating
Non-operating

IEC60068-2-27 (Test Ea, Unpackaged Shock):
10g
30g

Emissions

CISPR 11:
Group 1, Class A

ESD Immunity

IEC 61000-4-2:
8kV air discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 80MHz to 1000MHz
10V/m with 200Hz 50% Pulse 100%AM @ 900Mhz

EFT/B Immunity

IEC 61000-4-4:
+1kV @ 5kHz on power ports
+2kV @ 5kHz on signal ports
+2kV @ 5kHz on communications ports

Surge Transient
Immunity

IEC 61000-4-5:
+1kV line-line(DM) and +2kV line-earth(CM) on power ports
+1kV line-line(DM) and +2kV line-earth(CM) on signal ports
+2kV line-earth(CM) on shielded ports

Conducted RF
Immunity

IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHzto 80MHz