Span Your Valves

Chapter 9

9-18

6.

If the observed pressure HPS16 for pack and HPS33 for hold are still
not within 20% of setpoints HPC16 and HPC33, your pressure valve
is not linear over the desired range of operation. Correct for a
non-linear valve by adjusting the Selected Pressure Valve, Output for
Minimum: PKC43 for pack or HDC43 for hold as follows:

If actuals are at least 20%: And Your Selected

Valve is:

Then change PKC43 or HDC43

(N44:159 or N44:219) as follows

Less than setpoints

Direct Acting

Increase in 5% steps

Reverse Acting

Decrease in 5% steps

Greater than setpoints

Direct Acting

Decrease in 5% steps

Reverse Acting

Increase in 5% steps

To do this, change PKC43 and/or HDC43, download PKC and HDC
followed by HPC with bits B21/9, 10, 11, and repeat steps 3 and 4.

What You Have Accomplished

The open-loop tuning procedure you just completed has defined the:

range of ram (screw) backpressure during plastication

end-of-range maximum and minimum signal levels for linear control of

the plastication pressure valve in open-loop control

For this

range limit

When trying to obtain

the pressure in:

The QDC module drives the selected

pressure valve to % output signal in:

Minimum

PKC41 or HDC41

PKC43 or HDC43

Maximum

PKC42 or HDC42

PKC44 or HDC44

Now for all open-loop pack or hold pressure profiles, the QDC module
assumes a linear relationship between ram pressure and signal outputs.