Ground and shield your i/o devices – Rockwell Automation 1771-QDC, D17716.5.85(Passport) MNL. PLASTIC MOLDING MODULE User Manual

Page 28

Advertising
background image

Install the QDC Module

Chapter 2

2-9

Analog inputs and outputs are sensitive to electrical noise interference.
Take care to shield them properly.

Guidelines:

Use 22-gage (or larger) twisted-pair cable, 100% shielded with drain

wire, such as Belden 8761 (or equivalent). For cable distances over
50 ft, use 18-gage cable such as Belden 8760 (or equivalent)

Ground the cable shield at one end only; generally at the sensor or

amplifier end, not at the I/O chassis (see Figure 2.4 and Figure 2.5)

Figure 2.4

Shielding Differential Inputs

Connect the cable shield

and case ground to earth

ground at the Input Sensor

Input Sensor

18

17

14

QDC Module Input

+

10910Ć3

+15V

-15V

Do not connect.

Test purposes,

only.

10G

22M

22M

18v 18v

Ground and Shield

Your I/O Devices

Advertising