When You Use RSNetWorx for ControlNet Software

Keep the following in mind when you use RSNetWorx for ControlNet software.

1784-PKTCS Card Will Not Establish Connections Until Output Data is Initialized

The 1784-PKTCS card will not establish new or modified connections that require data to be
produced by the 1784-PKTCS card until the controlling application has initialized the output
data.
Examples of controlling applications include:

• RSView applications
• IOView test application
• Custom IOLinx applications

Examples of connection types that require output data from a controlling application include:

• Exclusive Owner connections to I/O racks
• Exclusive Owner connections to I/O modules
• Send Data connections

Examples of connection types that do not require output data from a controlling application
include:

• Input Only connections to I/O racks
• Input Only connections to I/O modules
• Listen Only connections to I/O racks
• Listen Only connections to I/O modules
• Receive Data From connections

For Information On This Topic

Refer To

Using The IOView Test Application

Chapter 6 of this manual

Creating Custom IOLinx Applications

the IOLinx Software Development Kit (catalog
number 9230-IOLINXSDK) online help

If The Controlling Application Has Not
Provided Output Data For A(n)

RSNetWorx for ControlNet Displays This Error
Message On The Connection Status Tab Of The Scan
List Configuration Screen

Exclusive Owner connection

No Originator Application Data Available

Send Data connection

No Target Application Data Available