7-2 Interpret Status Indicators

Publication 1784-IN042A-EN-P - April 2005

flashing - the indicator alternates between the two defined states (applies to each

indicator viewed independent of the other). If both indicators flash, they must flash
together, in phase.

Table 7.1 ControlNet status interpretation

A and

B

Cause:

Action:

off

• no power

• none or apply power to the PC

• 1784-PKTCS card

not configured

• Configure the card. See page 5-2.

• 1784-PKTCS

driver not
installed

• Install the driver. Refer to Chapter 3.

• faulted card

• check operating system event log for details

of fault (if the PC’s operating system supports
an event log)

• cycle power to the PC
• verify that you have firmly inserted the

1784-PKTCS card into a PCI local bus
expansion slot and that the expansion slot
screw is tightened

• if fault persists, contact your Rockwell

Automation representative or distributor

steady red

• faulted card

• check operating system event log for details

of fault (if the PC’s operating system supports
an event log)

• cycle power to the PC
• verify that you have firmly inserted the

1784-PKTCS card into a PCI local bus
expansion slot and that the expansion slot
screw is tightened

• if fault persists, contact your Rockwell

Automation representative or distributor

alternating red/green

• self-test

• none

alternating red/off

• incorrect node

configuration

• duplicate

ControlNet node
address

• check 1784-PKTCS node address and other

ControlNet configuration parameters

off

• channel disabled

• use RSNetWorx to configure the ControlNet

network for redundant media, if required