Interpret Status Indicators 7-3

Publication 1784-IN042A-EN-P - April 2005

1

UMAX is the highest node address on a ControlNet network that can transmit data.

steady green

• normal operation

• none

flashing green/off

• temporary

network errors

• check media for broken cables, loose

connectors, missing terminators, etc.

• if condition persists, refer to the ControlNet

Media Planning and Installation Manual,
publication CNET-IN002

flashing red/off

• media fault

• check media for broken cables, loose

connectors, missing terminators, etc.

• if condition persists, refer to the ControlNet

Media Planning and Installation Manual,
publication CNET-IN002

• no other nodes

present on
network

• add other nodes to the network

flashing red/green

• incorrect node

address

• change 1784-PKTCS node address so that it

is less than or equal to UMAX

1

• incorrect network

configuration

• use RSNetWorx to reconfigure the

ControlNet network so that UMAX

1

is greater

than or equal to the 1784-PKTCS node
address

Table 7.1 ControlNet status interpretation

A and

B

Cause:

Action: