Programming Instruction References

A-15

Instruction

Description

Parameter

Valid Addressing

Mode(s)

Valid File Types

Immediate

Values

OTE

Output Energize

bit address

direct, indirect

O, I, S, B, T, C, R,

N, A, ST, M

none

OTL

Output Latch

bit address

direct, indirect

O, I, S, B, T, C, R,

N, A, ST, M

none

OTU

Output Unlatch

bit address

direct, indirect

O, I, S, B, T, C, R,

N, A, ST, M

none

PID

PID

control block

direct

N

none

process variable

direct, indirect

O, I, B, T, C, R, N,

A

none

control variable

direct, indirect

O, I, B, T, C, R, N,

A

none

control block length

23 always

RAC

HSC Reset

Accumulator

counter

direct

C

none

source

direct, indirect

O, I, S, B, T, C, R,

N, A, ST, M

-32,768-32,767

fĆmin-fĆmax

RAD

Degrees to Ratians

source

direct, indexed direct

indirect, indexed indirect

O, I, S, B, T, C, R,

N, F, A, ST, M

-32,768-32,767

fĆmin-fĆmax

destination

direct, indexed direct

indirect, indexed indirect

O, I, S, B, T, C, R,

N, F, A, ST, M

none

REF

I/O Refresh

channel 0 (SLC

5/03 and SLC 5/04)

0=no, 1=yes

channel 1 (SLC

5/03 and SLC 5/04)

0=no, 1=yes

RES

Timer/Counter Reset

structure

direct

T, C, R

none

RET

Return

none

RPI

Reset Pending Interrupt slots

double hex word

(list of slots)

➁ Supported only by SLC 5/03 OS302 and SLC 5/04 OS401 processors.
➂ Supported only by MicroLogix 1000 controllers.
➆ Supported only by SLC 5/02, SLC 5/03, and SLC 5/04 processors.