Preface – Rockwell Automation 9323-PA2E APS SLC 500 Import/Export Utility User Manual User Manual

Page 94

Advertising
background image

Preface

APS Import/Export Utility User Manual

A-8

Instruction

Description

Parameter

Valid Addressing

Mode(s)

Valid File Types

Immediate

Values

DIV

Divide

source A

direct, indexed direct

indirect, indexed indirect

O, I, S, B, T, C, R,

N, F, A, ST, M

-32,768-32,767

fĆmin-fĆmax

source B

direct, indexed direct

indirect, indexed indirect

O, I, S, B, T, C, R,

N, F, A, ST, M

-32,768-32,767

fĆmin-fĆmax

destination

direct, indexed direct

indirect, indexed indirect

O, I, S, B, T, C, R,

N, F, A, ST, M

none

ENC

Encode 1 of 16 to 4

source

direct, indexed direct

indirect, indexed indirect

O, I, S, B, T, C, R,

N, A, ST, M

none

destination

direct, indexed direct

indirect, indexed indirect

O, I, S, B, T, C, R,

N, A, ST, M

none

EQU

Equal

source A

direct, indexed direct

indirect, indexed indirect

O, I, S, B, T, C, R,

N, F, A, ST, M

none

source B

direct, indexed direct

indirect, indexed indirect

O, I, S, B, T, C, R,

N, F, A, ST, M

-32,768-32,767

fĆmin-fĆmax

FFL

FIFO Load

source

direct, indexed direct

indirect, indexed indirect

O, I, S, B, T, C, R,

N, A, ST, M

-32,768-32,767

FIFO array

indexed direct

indexed indirect

O, I, S, B, N, A

none

FIFO control

direct

R

none

length

1-128

position

0-127

FFU

FIFO Unload

FIFO array

indexed direct

indexed indirect

O, I, S, B, N, A

none

destination

direct, indexed direct

indirect, indexed indirect

O, I, S, B, T, C, R,

N, A, ST, M

none

FIFO control

direct

R

none

length

1-128

position

0-127

➂ Supported only by MicroLogix 1000 controllers.
➃ Supported only by SLC 5/02, SLC 5/03, and SLC 5/04 processors and MicroLogix 1000 controllers.
➆ Indexed addressing is not allowed when using T, C, R, or M addresses.

Advertising