Rockwell Automation 9323-PA2E APS SLC 500 Import/Export Utility User Manual User Manual
Page 99
Programming Instruction References
A-13
Instruction
Description
Parameter
Valid Addressing
Mode(s)
Valid File Types
Immediate
Values
MSG
(5/03 and
Message
type
64=peerĆtoĆpeer
(5/03 and
5/04 only)
read/write
0=read, 1=write
target device
2=500CPU,
4=485CIF,
8=PLC5
local/remote
16=local,
32=remote
control block
direct
N
none
control block length
14
channel number
0 or 1
target node
0-31,
0-254 if 485CIF
remote bridge
link ID
0-254,
0 when local
remote bridge
node address
0-254
0 when local
local bridge node
address
0-254, 0xFFFF
when local
local file address
direct
O, I, S, B, T, C, R,
N, F, A, ST, M
➇
none
target file address
direct
O, I, S, B, T, C, R,
N, F, A, ST, M
➇
0-255
message length
O, I, S, B, N, A
➇
1-103
F
➇
1-51
T
1-34 or
if PLC5: 1-20
C, R
1-34
ST
➇
2 or
if PLC5: 1
message timeout
0-255
➇ File types F, A, and ST only apply to SLC 5/03 OS301 or later and SLC 5/04.