ArcShield Rating Labels

MCC units that have the arc resistant rating will carry a rating label on the
vertical wireway door. This label serves as the arc resistant nameplate and provides
information on the arc resistant rating. There will also be labels on other parts
that need to be in place before operating an arc resistant MCC.

Figure 7 - ArcShield Labels

Series Number and Series
ID as Manufactured in the
United States

ARC RESISTANT EQUIPMENT

ACCESSIBILITY: TYPE 2

ARC SHORT CIRCUIT CURRENT:

65 kA

ARC DURATION:

100 ms

OPERATIONAL VOLTAGE:

480 V

ARC FLASH HAZARD

DOORS AND COVERS MUST BE PROPERLY
CLOSED, LATCHED, AND SECURED.

EQUIPMENT MUST BE INSTALLED PER
MANUFACTURER’S INSTRUCTIONS. REFER TO
PUBLICATION 2100-IN012.

ONLY INSTALL ArcShield 100ms / 480V / 65kA
RATED UNITS IN THIS STRUCTURE.

EQUIPMENT WILL NOT FUNCTION AS
ARC RESISTANT IF ABOVE GUIDLINES
ARE NOT FOLLOWED.

FAILURE TO FOLLOW THESE GUIDELINES COULD
RESULT IN SEVERE INJURY OR DEATH.

41006-402-01 (1)

WARNING

PER IEEE C37.20.7-2007

ARC RESISTANT EQUIPMENT

ACCESSIBILITY

: TYPE 2

ARC SHORT CIRCUIT CURRENT

:

65 kA

ARC DURATION: DEVICE LIMITED
PROTECTIVE DEVICE

:

UL LISTED FUSES
CLASS L – FERRAZ-SHAWMUT A4BQ

1200 A

CLASS R – ANY FUSE

600 A

CLASS J – ANY FUSE

600 A

UL LISTED MOLDED CASE CIRCUIT BREAKERS
ALLEN-BRADLEY – BULLETIN 140U, FRAME I, JD, or K
CUTLER-HAMMER – SERIES C, FRAME F, J, K, L, M, or N

WARNING

PER IEEE C37.20.7 2007

ARC FLASH HAZARD

THE ARC CONTAINMENT CAPABILITY OF THE MOTOR

CONTROL CENTER IS DEPENDENT UPON THE MAIN

PROTECTIVE DEVICE. PROTECT ONLY WITH UL LISTED

PROTECTIVE DEVICE SPECIFIED ABOVE.

DOORS AND COVERS MUST BE PROPERLY CLOSED,

LATCHED, AND SECURED. EQUIPMENT MUST BE INSTALLED

PER MANUFACTURER’S INSTRUCTIONS.

REFER TO PUBLICATION 2100-IN012.

EQUIPMENT WILL NOT FUNCTION AS ARC RESISTANT IF

ABOVE GUIDELINES ARE NOT FOLLOWED.

FAILURE TO FOLLOW THESE GUIDELINES COULD RESULT IN

SEVERE INJURY OR DEATH.

41006-401-01 (1)

100 ms Arc Duration

Device Limited Rating

ATTENTION: Read tables

1

through

4

before adding new sections or

units to an existing CENTERLINE MCC.

Table 1 - Sections

Series
Letter

Scope

Description of Change

Date Implemented
in the U.S.

A

(1)

Original design

February 1971

B

(1)

All

Changed terminal blocks

November 1976

C

(1)

All

Elimination of external mounting channels

June 1979

D

(1)

All

Reverse fed 2192 and 2193

April 1981

E

(1)

All

Redesign

gasketing

October 1982

F

(1)

All

Modified top horizontal wireway pan to accept units with handle interlock in topmost space factor

October 1983

G

(1)

42K

42 k bracing-incorporates new bus support and cover

January 1985

G

(1)

65K

65 k bracing-incorporates new bus support and cover

July 1985

H

All

New hinge design

January 1986

J

All

Changed handle, operating mechanism, and circuit breaker to Cutler-Hammer series C, 150 A, 250 A, 400 A
frame

October 1986

K

All

Changed to new unit grounding system

May 1990

L

All

Changed to new 600…1200 A circuit breaker operating mechanism

February 1996