Required minimum electrical spacing – Rockwell Automation 2100 CENTERLINE Low Voltage Motor Control Centers  User Manual

Page 85

Advertising
background image

Rockwell Automation Publication 2100-IN012E-EN-P - February 2012

85

Final Checklist Before Energizing Chapter 7

Required Minimum
Electrical Spacing

.

Table 7 - Electrical Spacing Requirements for MCCs

(1)

(1) An isolated dead metal part, such as a screw head or a washer, interposed between uninsulated parts of

opposite polarity or between an uninsulated live part and grounded dead metal, is considered to reduce the
spacing by an amount equal to the dimension of the interposed part along the path of measurement.

Voltage

Min Spacing, in. (mm)

Between Live Parts of Opposite Polarity

Between Live Parts and

Grounded Metal Parts,

Through Air and Over

Surface

Through Air

Over Surface

0…150

0.5 in. (12.7 mm)

0.75 in. (19.1 mm)

0.5 in. (12.7 mm)

151…300

0.75 in. (19.1 mm)

1.25 in. (31.8 mm)

0.5 in. (12.7 mm)

301…600

1.0 in. (25.4 mm)

2.0 in. (50.8 mm)

1.0 in. (25.4 mm)

(2)

(2) A through-air spacing of not less than 0.5 in. (12.7 mm) is acceptable.

at a circuit-breaker or fusible disconnecting means
between grounded dead metal and the neutral of a 3-phase, 4-wire motor control center

601…1000

(3)

(3) Applies only to rectified output >600V DC.

1.5 in. (38 mm)

2.5 in. (63 mm)

(4)

(4) Through-air spacing required is 1.5 in. (38 mm); over-surface spacing required is 2.0 in. (50 mm).

Table 8 - Spacing Requirements within MCC Units

Voltage

Min Spacing, in. (mm)

Between Uninsulated Live Parts of

Opposite Polarity and Between an

Uninsulated Live Part and an Exposed or

Uninsulated Dead Metal Part other than

the Enclosure

Between Uninsulated Live

Parts and the Walls of a Metal

Enclosure

(1)

, Including Fittings

for Conduit or Armored Cable

(1) The enclosure refers to the section enclosure.

Through Air

Over Surface

Shortest Distance

0…150

0.125 in. (3.2 mm)

(2)

(2) The spacing between wiring terminals of opposite polarity shall not be less than 0.25 in. (6.4 mm) if the

terminals are in the same plane. A metal piece attached to the enclosure shall be considered to be a part of the
enclosure for the purpose of this note if deformation of the enclosure is likely to reduce the spacing between the
metal piece and a live part.

0.25 in. (6.4 mm)

0.5 in. (12.7 mm)

151…300

0.25 in. (6.4 mm)

0.375 in. (9.5 mm)

0.5 in. (12.7 mm)

301…600

0.375 in. (9.5 mm)

0.5 in. (12.7 mm)

0.5 in. (12.7 mm)

601…1000

(3)

(3) DC circuits derived from rectified AC circuits without increases to the peak nominal voltage may comply with

the electrical spacings of the AC supply voltage.

0.55 in. (14 mm)

0.85 in (21.6 mm)

(4)

(4) Through-air spacing required is 0.8 in. (20.3 mm); over-surface spacing required is 1.0 in. (25.4 mm).