Rockwell Automation 2100 CENTERLINE Low Voltage Motor Control Centers  User Manual

Page 35

Advertising
background image

Rockwell Automation Publication 2100-IN012E-EN-P - February 2012

35

Installation Procedures Chapter 2

Figure 20 - Mounting Dimensions for 71 in. H (reduced height) MCC Sections

A

D

C

B

E

20 in.
(508 mm)

20 in.
(508 mm)

70.48 in.
(1790.19 mm)

70.48 in.
(1790.19 mm)

0.25 in. (6 mm)

0.25 in. (6 mm)

71 in. High Section
(1803.4 mm)

Dimension,

approx.

Section Depth

15 in. (381 mm) Deep

in. (mm)

20 in.(635 mm) Deep

in. (mm)

A

15.00 (380)

20.00 (508)

B

14.75 (374)

19.75 (500)

C

5.12 (130)

10.12 (256)

D

4 (101)

8 (203)

E

4.40 (112)

Advertising