Rockwell Automation Publication 2100-IN012E-EN-P - February 2012

83

Final Checklist Before Energizing Chapter 7

Figure 47 - ArcShield Components

41006-404-01 (1)

HOT GASES MAY BE EXHAUSTED IF AN INTERNAL
ARCING FAULT OCCURS.

WARNING

ARC RESISTANT EQUIPMENT

ACCESSIBILITY: TYPE 2

ARC SHORT CIRCUIT CURRENT:

65 kA

ARC DURATION:

100 ms

OPERATIONAL VOLTAGE:

480 V

ARC FLASH HAZARD

DOORS AND COVERS MUST BE PROPERLY
CLOSED, LATCHED, AND SECURED.

EQUIPMENT MUST BE INSTALLED PER
MANUFACTURER’S INSTRUCTIONS. REFER TO
PUBLICATION 2100-IN012.

ONLY INSTALL ArcShield 100ms / 480V / 65kA
RATED UNITS IN THIS STRUCTURE.

EQUIPMENT WILL NOT FUNCTION AS
ARC RESISTANT IF ABOVE GUIDLINES
ARE NOT FOLLOWED.

FAILURE TO FOLLOW THESE GUIDELINES COULD
RESULT IN SEVERE INJURY OR DEATH.

41006-402-01 (1)

WARNING

PER IEEE C37.20.7-2007

ARC RESISTANT EQUIPMENT

ACCESSIBILITY

: TYPE 2

ARC SHORT CIRCUIT CURRENT

:

65 kA

ARC DURATION: DEVICE LIMITED
PROTECTIVE DEVICE

:

UL LISTED FUSES
CLASS L – FERRAZ-SHAWMUT A4BQ

1200 A

CLASS R – ANY FUSE

600 A

CLASS J – ANY FUSE

600 A

UL LISTED MOLDED CASE CIRCUIT BREAKERS
ALLEN-BRADLEY – BULLETIN 140U, FRAME I, JD, or K
CUTLER-HAMMER – SERIES C, FRAME F, J, K, L, M, or N

WARNING

PER IEEE C37.20.7 2007

ARC FLASH HAZARD

THE ARC CONTAINMENT CAPABILITY OF THE MOTOR

CONTROL CENTER IS DEPENDENT UPON THE MAIN

PROTECTIVE DEVICE. PROTECT ONLY WITH UL LISTED

PROTECTIVE DEVICE SPECIFIED ABOVE.

DOORS AND COVERS MUST BE PROPERLY CLOSED,

LATCHED, AND SECURED. EQUIPMENT MUST BE INSTALLED

PER MANUFACTURER’S INSTRUCTIONS.

REFER TO PUBLICATION 2100-IN012.

EQUIPMENT WILL NOT FUNCTION AS ARC RESISTANT IF

ABOVE GUIDELINES ARE NOT FOLLOWED.

FAILURE TO FOLLOW THESE GUIDELINES COULD RESULT IN

SEVERE INJURY OR DEATH.

41006-401-01 (1)

Pressure Relief Vent
(100 ms ArcShield rating only)

ArcShield Door Latches

Support Pan Screws

Support Brackets

Frame-mount Support

ArcShield Rating Label

Back Corner Baffles
(end of lineup only)

Vertical Support Angle
(end of lineup)

Vertical Wireway Baffle

Top and Bottom Horizontal
Wireway U-nuts

100 ms Rating

Device Limited
Rating

Advertising