26

Rockwell Automation Publication 2100-IN012E-EN-P - February 2012

Chapter 2 Installation Procedures

Figure 12 - Mounting Dimensions for 15 in. and 20 in. Sections - continued

The optional external mounting channels add 1.5 in. (38.1 mm) to the height.

(2) Mounting Slots
0.56 in. x 1.13 in. Slots
(14 mm x 29 mm) Slots

A

D

D

B

C

E

E

Rear

Front

For seismic bolt-down applications: first
section of the MCC lineup.

For seismic bolt-down applications: last section of
the MCC lineup, extra bolt-down locations (2 bolts).

Standard Ground Bus

7.38 in.
(187 mm)

0.25 in.
(6.35 mm)

Dimensions
approx.

15 in. Deep

20 in. Deep

20 in. Wide

in. (mm)

25 in. Wide

in. (mm)

30 in. Wide

in. (mm)

35 in. Wide

in. (mm)

20 in. Wide

in. (mm)

25 in. Wide

in. (mm)

30 in. Wide

in. (mm)

35 in. Wide

in. (mm)

A

20.00 (508)

25.00 (635)

30.00 (762)

35.00 (889)

20.00 (508)

25.00 (635)

30.00 (762)

35.00 (889)

B

15.00 (381)

15.00 (381)

15.00 (381)

15.00 (381)

20.00 (508)

20.00 (508)

20.00 (508)

20.00 (508)

C

11.56 (294)

11.56 (294)

11.56 (294)

11.56 (294)

16.56 (421)

16.56 (421)

16.56 (421)

16.56 (421)

D

10.00 (254)

12.50 (318)

15.00 (381)

17.50 (445)

10.00 (254)

12.50 (318)

15.00 (381)

17.50 (445)

E

(1)

9.25 (235)

11.75 (299)

14.25 (362)

16.75 (426)

9.25 (235)

11.75 (299)

14.25 (362)

16.75 (426)

(1) Applies to first and last sections that require seismic ratings.