Rockwell Automation Publication 2100-IN012E-EN-P - February 2012

21

General Information Chapter 1

Storage and Operation

CENTERLINE MCCs conform to NEMA standard ICS 1-2000 for service and
storage conditions. All MCCs should operate in an ambient temperature above
0

o

C (32

o

F) but not exceeding 40

o

C (104

o

F) at 95% non-condensing humidity.

If the equipment is stored, the ambient temperature should remain above
-30

o

C (-22

o

F) but not exceed 65

o

C (149

o

F). In addition, MCCs have an

altitude class of 2 km (1 km for MCCs that contain variable frequency drives).
The altitude class of 2 km designates equipment for installation where the
altitude does not exceed 2000 m (6600 ft). For installation above
2000 m (6600 ft), contact Rockwell Automation LV MCC Technical Support at
1.440.646.5800 and follow the prompts to Allen-Bradley>Low Voltage Motor
Control Centers>Post Shipment Support.