Rockwell Automation 2100 CENTERLINE Low Voltage Motor Control Centers User Manual
Page 51

Rockwell Automation Publication 2100-IN012E-EN-P - February 2012
51
Installing and Removing Plug-in Units Chapter 4
3.
Open the door completely.
4.
Remove the unit door, if necessary.
a. Remove the door-mounted devices and wiring, if necessary.
b. Remove the hinge pins by sliding upward with a flathead screwdriver.
TIP
It is not necessary to remove the unit door to remove a unit from a
section. However, these steps may still be necessary even when
the door is not removed.
For Units With
Follow This Step
A control station
First slide the hinge pin out of the hinge and through the tab on
the control station wiring.
ArcShield units with
100 ms arc duration
rating
Two hinges are required for each hinge leaf.
1. The upper hinge on each door must be removed from the
structure to remove the uppermost hinge pin.
2. Remove the hinge pin through the lower hinge, then through
the hinge leaf and upper hinge.
Only top hinge
must be removed
to install hinge
pin.
Hinge
Hinge Pin
Hinge Leaf
Hinge for ArcShield Units with 100 ms Arc Duration Rating