Group 3 parameters, Pr-3.00 follower configuration – Rockwell Automation 2092-DAx Ultra1500 User Manual User Manual
Page 186

Publication 2092-UM001D-EN-P — July 2005
D-22
Ultra1500 Operator Interface
Group 3 Parameters
Group 3 Parameters provide position control settings.
Pr-3.00 Follower Configuration
Data Size:
4 digits
Digit 0:
Command Type
Range:
Value
Description
0x0
CW + CCW, Positive logic
0x1
CW + CCW, Negative logic
0x2
Pulse Line + Sign, Positive Logic
0x3
Pulse Line + Sign, Negative Logic
0x4
A Phase + B Phase, Positive Logic
0x5
A Phase + B Phase, double input
multiplication, Positive Logic
0x6
A Phase + B Phase, quadruple input
multiplication, Positive Logic
Default:
0x0
Note:
For values 0x4, 0x5, and 0x6, Motor Counts = :
Master Lines * MULT * [(4 * Pr-3.01)/Pr-3.02]
Where the multiplier (MULT) is 1, 2, and 4 for values 0x4, 0x5,
and 0x6 respectively.
Applicable Operating Mode:
Follower
Digit 1:
Controller Output Type
Range:
Value
Description
0
Line Drive
1
Open Collector
Default:
0
Applicable Operating Mode:
Follower
Digit 2:
Encoder Output Forward Direction
Range:
Value
Description
0
During Forward Rotation, Encoder
Output Phase A have a lead of 90× over
Phase B.
1
During Forward Rotation, Encoder
Output Phase B have a lead of 90× over
Phase A.
Default:
0
Applicable Operating Mode:
All
Digit 3:
Reserved