Determining your type of input power, Grounded power configuration, Determining your type of input power -3 – Rockwell Automation 2092-DAx Ultra1500 User Manual User Manual
Page 61: Grounded power configuration -3

Publication 2092-UM001D-EN-P — July 2005
Connecting Your Ultra1500
3-3
Determining Your Type of
Input Power
Before you wire your Ultra1500 system you must determine the type of input
power you are connecting to. The Ultra1500 is designed to operate only in
grounded environments.
Grounded Power Configuration
The grounded power configuration allows you to ground your single-phase or
three-phase power at a neutral point. Match your secondary to one of the
examples below and be certain to include the grounded neutral connection.
Figure 3.1
Three-Phase Power Configuration (WYE Secondary)
Figure 3.2
Three-Phase Grounded Power Configuration (Delta Secondary)
L1
L2
L3
Bonded cabinet
ground bus
Transformer (WYE) Secondary
Ground grid or
power distribution ground
Ultra1500 Three-Phase AC Input
2092-DA4 and -DA5
L1, L2, and L3 Terminals
L1
L2
L3
L1
L3
L2
Transformer (Delta) Secondary
Ground Grid or Power Distribution Ground
Ultra1500 Three-Phase AC Input
2092-DA4 and -DA5
L1, L2, and L3 Terminals
Bonded Cabinet Ground Bus
Transformer (Delta) Secondary
Ultra1500 Three-Phase AC Input
2092-DA4 and -DA5
L1, L2, and L3 Terminals