Ventilation requirements, Ventilation requirements -8 – Rockwell Automation 2092-DAx Ultra1500 User Manual User Manual
Page 20

Publication 2092-UM001D-EN-P — July 2005
1-8
Installing Your Ultra1500
Ventilation Requirements
This section provides information to assist you in sizing your cabinet and
locating your Ultra1500 drive(s) inside the cabinet.
Figure 1.2
Minimum Clearance Requirements
Refer to Appendix A for Ultra1500 power dissipation specifications.
50.0 mm (1.97 in.) clearance
for airflow and installation
50.0 mm (1.97 in.) clearance
for airflow and installation
Allow 10.0 mm (0.39 in.)
between drives
Minimum cabinet depth:
2092-DA1, -DA2, and -DA3 = 216 mm (8.52 in.)
2092-DA4, and -DA5 = 261 mm (10.28 in.)
Do not mount drive on its side.
Ultra1500s mounted
vertically on the panel
Allow 30.0 mm (1.18 in.)
from adjacent wall
IMPORTANT
If the cabinet is ventilated, use filtered or conditioned air to
prevent the accumulation of dust and dirt on electronic
components. The air should be free of oil, corrosives, or
electrically conductive contaminates.