2 electrical description – Rockwell Automation Current Input Module User Manual

Page 11

Advertising
background image

2Ć3

2.2

Electrical Description

The module provides sixteen channels of 4Ć20 mA analog current

information to AutoMax andAutoMate systems. Each channel

consists of a pair of high impedance measurement inputs. The

sixteen current inputs share the same common. This analog common

has 2500 VAC of isolation from the system common. See figure 2.2.

An external userĆsuppliedpower supply is requiredfor the 4Ć20 mA

transmitters. Terminal boardassemblies (M/N 61C549 and61C550)

have terminals available for both a primary power supply anda

backup power supply. The backup supply is optional. The two power

supplies are diodeĆisolated as shown in figure 2.2.
The sixteen pairs of inputs are multiplexedto an instrumentation

amplifier which drives a thirteenĆbit plus sign bit A/D converter.
The data register (registers 0 to 15) of a configured channel is

updatedwhen the onĆboardprocessor converts andaverages

together approximately 166 samples (60 Hz) or 200 samples (50 Hz)

of the channel input. In this manner, line frequency noise at the input

of the A/D converter is integratedout of the result that is providedto

the system. This overĆsampling of the analog inputs also simplifies

the filter requirements. A single pole analog filter is locatedon each

measurement input line. The line frequency filter can be disabled on

a perĆchannel basis via register 31 for a faster response time.
The module also contains three voltage references for A/D converter

calibration. These references are checkedprior to each scan of the

configuredchannels, andthe calibration coefficients are updated

accordingly. All nonĆzero references are derived from the A/D

converter's buriedĆzener reference. No potentiometer adjustments

are requiredto maintain the specifiedaccuracy.
The onĆboardprocessor averages the raw A/D converter data,

linearizes the average using the calibration coefficients, andthen

adjusts the reported output value per the userĆselectable scaling

values. If scaling values are not used, the reported output value will

be in the range 0 to 4095. This value will then either be written to the

appropriate channel data register (registers 0Ć15), or it will become

part of the running average specifiedin register 26. If a running

average is specifiedin register 26, the reportedoutput value in the

channel data register is the averaged data value.
The module can also be configured, on a perĆchannel basis, to

provide square root extraction on the input signal. This provides flow

information directly from differential pressure inputs.
A broken wire from a transmitter is indicated through an outĆofĆrange

status bit in register 20. The module also provides high and low limit

registers which can be set by the user. Status registers then indicate

when the desired high/low values have been exceeded.
All read operations on the module's memory include a parity test.

Failure of the parity test results in a system shutdown. Processor

modules can read all locations within the slot address but can only

write to registers 23 through 31.
The module will execute a full set of powerĆup diagnostics which

must execute successfully before the module can go into the run

mode.

Advertising