Channel 2: Operating Pressure
Process Parameters
Configuration Values
D Maximum = 1960 psig
Reg. 24 = 10000 (Scaled in
0.01% of span)
D Minimum = 1940 psig
Reg. 25 = 0
D High High Alarm = 1958 psig Reg. 27 = 9000
D High Alarm = 1955 psig
Reg. 28 = 7500
D Low Alarm = 1945 psig
Reg. 29 = 2500
D Low Low Alarm = 1942 psig
Reg. 30 = 1000
If you are using AutoMax version 2.1 or earlier, you will need to define
common (systemĆwide) variables in a configuration task before
writing an application task. The configuration task in Appendix E
defines the common variables in the sample task below.
If you are using DCS 5000/AutoMax version 3.0 or later, this
information will be entered in the configuration form using the
Programming Executive software.