4Ć17

Channel 2: Operating Pressure
Process Parameters

Configuration Values

D Maximum = 1960 psig

Reg. 24 = 10000 (Scaled in

0.01% of span)

D Minimum = 1940 psig

Reg. 25 = 0

D High High Alarm = 1958 psig Reg. 27 = 9000
D High Alarm = 1955 psig

Reg. 28 = 7500

D Low Alarm = 1945 psig

Reg. 29 = 2500

D Low Low Alarm = 1942 psig

Reg. 30 = 1000

If you are using AutoMax version 2.1 or earlier, you will need to define

common (systemĆwide) variables in a configuration task before

writing an application task. The configuration task in Appendix E

defines the common variables in the sample task below.
If you are using DCS 5000/AutoMax version 3.0 or later, this

information will be entered in the configuration form using the

Programming Executive software.