0 programming, 1 register organization – Rockwell Automation Current Input Module User Manual

Page 19

Advertising
background image

4Ć1

4.0 PROGRAMMING

This section describes how the data is organized in the module and

provides examples of how the module is accessed by application

programs.
For DCS 5000 and AutoMax version 2.1 and earlier, you must assign

variable names to registers by writing a configuration task. For

AutoMax version 3.0 and later, you define registers using the

ReSourcet AutoMax Programming Executive. After these variables

are defined, you can generate the configuration file automatically,

which eliminates the requirement to write a configuration task for the

rack. If you are using AutoMax version 2.1 or earlier, refer to

Appendix F for a sample current input configuration task. If you are

using AutoMax version 3.0 or later, refer to the AutoMax

Programming Executive Instruction Manual (JĆ3750) for more

information. Note that AutoMate systems require no special

configuration procedure to use the current input module.
For additional programming information refer to the AutoMate 30/40

Software Instruction Manual (JĆ3150), the DCS 5000/AutoMax

Configuration Task Instruction Manual (JĆ3649), or the AutoMax

Programming Executive Manual (JĆ3750).

4.1

Register Organization

The Current Input module uses 32 registers to store and organize its

data. The same registers are used whether the module is in a local

rack or a remote rack. See Table 4.1 for a list of the registers. Note

that writing to a read only" register will result in an I/O error. Table

4.2 contains a list of register default values. When the module is used

in a DCS 5000/AutoMax system and a Stop All command is received,

the module will be placed in a power up state which will reset all 32

registers to their default values.

Advertising