4Ć13

4.2

Analog Input Channel Configuration

Procedure

Analog input channel configuration information is stored onĆboard

the Current Input module. At system powerĆup, default values are

automatically placed in the module's memory. You can change these

default values on a channelĆbyĆchannel basis. See figure 4.11.
To do this, you need to set bits 12 to 15 of register 31 equal to zero to

make sure the Current Input module is in the READY state and then

place a value in registers 23 through 31 for each analog input

channel you wish to configure:
D Channel Number Register (Register 23)
D Maximum Scaling Value (Register 24)
D Minimum Scaling Value (Register 25)
D Number of Samples Register (Register 26)
D High High Alarm Register (Register 27)
D High Alarm Register (Register 28)
D Low Alarm Register (Register 29)
D Low Low Alarm Register (Register 30)
D Configuration Command Register (Register 31)
After you have placed values in registers 23 through 30 and put the

write Configuration Command Code into register 31, the system

automatically transfers the new channel parameters to the

appropriate locations in memory. To use these parameters on

another unconfigured channel, simply change the channel number

and put the write Configuration Command Code into register 31. If

you want to configure a channel with the original powerĆup default

values, you must first place the read Configuration Command Code

in register 31 to restore these values to registers 23 through 30. Note

that the channels on the Current Input module must be configured

from only one application program.