Rockwell Automation Current Input Module User Manual

Page 38

Advertising
background image

4Ć20

4.5

Sample AutoMate Current Input

Application Program

The sample AutoMate current input application program in figure

4.13 is written for a Current Input module in a remote rack that is

controlled by an AutoMate 40 processor. If your system uses an

AutoMate 30 processor, the addresses you would use must be

changed accordingly. If the Current Input module is in a local rack,

LOCIN/LOCOUT commands would replace the REMIN/REMOUT

commands. Refer to the A30/A40 Software Reference Manual

(JĆ3150) for additional information.
In the sample AutoMate program, the Current Input module is

connected to three 4Ć20 mA transmitters which are wired into a

pressure polymerization process.
One transmitter is used to sense the level of the material in the

reactor. The second transmitter has its span calibrated for 0 to 3000

psig (gauge poundsĆperĆsquare inch) and is used during startup

operation. The third transmitter has its span calibrated for 1940 to

1960 psig and is used for process control.
Channel 0: Material Level
Process Parameters

Configuration Values

D Maximum = 20 feet

Reg. 24 = 2000 (Scaled in

ąąą0.01 Ft)

D Minimum = - 1 feet

Reg. 25 = -100

D High High Alarm = 18 feet

Reg. 27 = 1800

D High Alarm = 16 feet

Reg. 28 = 1600

D Low Alarm = 4 feet

Reg. 29 = 400

D Low Low Alarm = 0 feet

Reg. 30 = ăă0

Channel 1: Startup Pressure
Process Parameters

Configuration Values

D Maximum = 3000 psig

Reg. 24 = 3000 (Scaled

ąąądirectly in psig)

D Minimum = 0 psig

Reg. 25 = ăăă0

D High High Alarm = 2500 psig Reg. 27 = 2500
D High Alarm = 2000 psig

Reg. 28 = 2000

D Low Alarm = 500 psig

Reg. 29 = ă500

D Low Low Alarm = 250 psig

Reg. 30 = ă250

Channel 2: Operating Pressure
Process Parameters

Configuration Values

D Maximum = 1960 psig

Reg. 24 = 10000 (Scaled in

ąąą0.01% of span)

D Minimum = 1940 psig

Reg. 25 = ăăă0

D High High Alarm = 1958 psig Reg. 27 = 9000
D High Alarm = 1955 psig

Reg. 28 = 7500

D Low Alarm = 1945 psig

Reg. 29 = 2500

D Low Low Alarm = 1942 psig

Reg. 30 = 1000

Advertising