0 diagnostics and troubleshooting, 1 incorrect data – Rockwell Automation Current Input Module User Manual

Page 49

Advertising
background image

5Ć1

5.0 DIAGNOSTICS AND

TROUBLESHOOTING

This section explains how to troubleshoot the module and field

connections. If you cannot correct the problem usingthe instructions

below, the module is not userĆserviceable. If the procedure calls for a

component to be swapped with a replacement part and the problem

is not corrected, replace the original component and go on to the

next step.

5.1

Incorrect Data

Problem: The data is always on, always off, or different than

expected. The possible causes of this are a module in the wrongslot,

a programming error, or a malfunctioning module. It is also possible

that the transmitter is either not wired or is wired incorrectly. Use the

followingprocedure to isolate the problem:
Step 1.

Connect the programming terminal to the system and run

the ReSource Software. Determine whether the channel is

configured by examining register 21. If it is not, use the

procedure in section 4.2 to configure the channel.

Step 2.

For DCS 5000/AutoMax systems, verify that the module

configuration is correct. Verify that the Current Input

module is in the correct slot.
Verify that the slot number beingreferenced agrees with

the slot number of the module.
For remote I/O installations, verify that the master slot and

remote drop numbers are defined correctly.

Step 3.

Verify that the field wiringis properly connected.

DANGER

THIS EQUIPMENT IS AT LINE VOLTAGE WHEN AĆC POWER IS CONNECTED.

DISCONNECT AND LOCK OUT ALL UNGROUNDED CONDUCTORS OF THE AĆC

POWER LINE. FAILURE TO OBSERVE THESE PRECAUTIONS COULD RESULT IN

SEVERE BODILY INJURY OR LOSS OF LIFE.

Turn off power to the module.
Confirm that all terminal board connections are tight.
Check the cables for continuity between the faceplate

connector and the terminal board assembly.
Turn on power to the module.

Step 4.

Check for an input out of range condition.
Monitor register 20. Use the MONITOR function in

DCS 5000/AutoMax systems or the POINT MONITOR

function in AutoMate systems.

Advertising