4Ć5

4.1.3

High Alarm Status Register (Register 17)

Register 17 indicates the current status of each configured channel's

High alarm. See figure 4.3. A bit is set in this register whenever a

channel's input value exceeds the configured High alarm limit. The

bit is reset when the input value returns to a level below or equal to

the configured limit.

Register 17

Bits 0Ć15

14 13 12 11 10 9

8

7

6

5

4

3

2 1

0

R

R

R

R R

R

R

R

R R

R

R R

R R R

Bit 5 = Channel 5
Bit 6 = Channel 6
Bit 7 = Channel 7
Bit 8 = Channel 8
Bit 9 = Channel 9

Bit 10 = Channel 10
Bit 11 = Channel 11
Bit 12 = Channel 12
Bit 13 = Channel 13
Bit 14 = Channel 14
Bit 15 = Channel 15

Bit 0 = Channel 0
Bit 1 = Channel 1
Bit 2 = Channel 2
Bit 3 = Channel 3
Bit 4 = Channel 4

15

Figure 4.3 Ć High Alarm Status Register

4.1.4

Low Alarm Status Register (Register 18)

Register 18 indicates the current status of each configured channel's

Low alarm. See figure 4.4. A bit is set in this register whenever a

channel's input value is less than the configured Low alarm limit. The

bit is reset when the input value returns to a level equal to or above

the configured limit.

Register 18

Bits 0Ć15

14 13 12 11 10 9

8

7

6

5

4

3

2 1

0

R

R

R R R R

R

R

R R

R

R R

R R R

Bit 5 = Channel 5
Bit 6 = Channel 6
Bit 7 = Channel 7
Bit 8 = Channel 8
Bit 9 = Channel 9

Bit 10 = Channel 10
Bit 11 = Channel 11
Bit 12 = Channel 12
Bit 13 = Channel 13
Bit 14 = Channel 14
Bit 15 = Channel 15

Bit 0 = Channel 0
Bit 1 = Channel 1
Bit 2 = Channel 2
Bit 3 = Channel 3
Bit 4 = Channel 4

15

Figure 4.4 Ć Low Alarm Status Register