Register 3005 = Register contains the current input channel's High

High alarm value. This value is provided by the

data table in the 5000Ćseries registers.

Register 3006 = Register contains the current input channel's High

alarm value. This value is provided by the data

table in the 5000Ćseries registers.

Register 3007 = Register contains the current input channel's Low

alarm value. This value is provided by the data

table in the 5000Ćseries registers.

Register 3010 = Register contains the current input channel's Low

Low alarm value. This value is provided by the

data table in the 5000Ćseries registers.

Register 3011 = Register contains the current input channel's

configuration command. This value is provided by

the data table in the 5000Ćseries registers.

Registers 3100 to 3137Ă=Registers contain the data read from the

Current Input module.

Registers 5000 to 5027Ă=Registers contain the data used to

configureĂthe current input channels. Each

channelĂuses eight registers:

Max.

Scale

Min.

Scale

Average

Samples

High

High

High

Low

Low

Low

Config.

Command

Reg. 5000ă=Ăă2000

Reg. 5010ă=Ăă3000

Reg. 5020ă=Ă10000

-100

0

0

20

20

20

1800

2500

9000

1600

2000

7500

ă400

ă500

2500

ăă0

ă250

1000

12288*

12288ă

12288ă

*12288 = 3000 Hex

Note that you must use the POINTMONITOR function to enter these

values into the 5000Ćseries registers before you begin executing the

program.
Register 5200 = Register contains the value (0) for the READY

command.