Rockwell Automation Current Input Module User Manual

Page 25

Advertising
background image

4Ć7

4.1.7

Channel Configuration Status Register

(Register 21)

Register 21 indicates whether or not a channel has been configured.

See figure 4.7. A bit is set in this register when a channel receives a

correct writeĆconfiguration command. The bit remains set until it is

cleared by a reset configuration command from register 31.

Register 21

Bits 0Ć15

14 13 12 11 10

9

8

7

6

5

4

3

2 1

0

R

R

R R R R

R

R

R R

R

R R

R R R

Bit 5 = Channel 5
Bit 6 = Channel 6
Bit 7 = Channel 7
Bit 8 = Channel 8
Bit 9 = Channel 9

Bit 10 = Channel 10
Bit 11 = Channel 11
Bit 12 = Channel 12
Bit 13 = Channel 13
Bit 14 = Channel 14
Bit 15 = Channel 15

Bit 0 = Channel 0
Bit 1 = Channel 1
Bit 2 = Channel 2
Bit 3 = Channel 3
Bit 4 = Channel 4

15

Figure 4.7 Ć Channel Configuration Status Register

4.1.8

Configuration Status Register (Register 22)

Register 22 provides the status of the configuration command issued

by register 31. See figure 4.8. Bit 15 is set in this register whenever a

channel receives a configuration command. Error bit 14 will be set if

an incorrect configuration command is detected.

Register 22

Bits 0Ć15

14 13 12 11 10 9

8

7 6

5 4

3

2 1

0

R

R

R

R R

R

R

R R R

R R R R

R R

Bit 0 = Channel Number Error

Bit 1 = llegal Running Average Number Error

Bit 2 = Low Low Alarm Value Is Not the Lowest

Bit 3 = High Alarm Value Is Not Larger Than The Low Alarm Value

Bit 4 = High High Alarm Value Is Not the Highest

Bit 5 = Alarm Value is Out Of Range Of The Scaling Range

Bit 6 = Illegal Configuration Command

Bit 7 = READYState Not Enabled

Bit 8 = Maximum Scaling Value Must Be At Least 100 Greater Than The

Minimum Scaling Value

Bit 9 to 13= Not Used

Bit 14 =ĂConfiguration Error

Bit 15 =ĂConfiguration Is Complete

15

Figure 4.8 Ć Configuration Status Register

Advertising