4.1.5

Low Low Alarm Status Register (Register 19)

Register 19 indicates the current status of each configured channel's

Low Low alarm. See figure 4.5. A bit is set in this register whenever a

channel's input value is less than the configured Low Low alarm limit.

The bit is reset when the input value returns to a level equal to or

abovetheconfigured limit.

Register 19

Bits 0Ć15

14 13 12 11 10 9

8

7

6

5

4

3

2 1

0

R

R

R R R R

R

R

R R

R R R

R R R

Bit 5 = Channel 5
Bit 6 = Channel 6
Bit 7 = Channel 7
Bit 8 = Channel 8
Bit 9 = Channel 9

Bit 10 = Channel 10
Bit 11 = Channel 11
Bit 12 = Channel 12
Bit 13 = Channel 13
Bit 14 = Channel 14
Bit 15 = Channel 15

Bit 0 = Channel 0
Bit 1 = Channel 1
Bit 2 = Channel 2
Bit 3 = Channel 3
Bit 4 = Channel 4

15

Figure 4.5 Ć Low Low Alarm Status Register

4.1.6

Out of Range Status Register (Register 20)

Register 20 indicates the current status of each configured channel's

Out of Range alarm. See figure 4.6. A bit is set in this register

whenever a channel's A/D input value is outside of the range of

3.7 mA to 20.3 mA. The bits in this register are not latched

automatically. If you want a bit to belatched thefirst timea value

goes out of range, you must latch it through the application program.
If an input is identified as being out of range, the most probable

causeis that a wirebetween thetransmitter and themodulehas

either not been properly connected or has been broken.

Register 20

Bits 0Ć15

14 13 12 11 10 9

8

7

6

5

4

3

2 1

0

R

R

R R R R

R

R

R R

R

R R

R R R

Bit 5 = Channel 5
Bit 6 = Channel 6
Bit 7 = Channel 7
Bit 8 = Channel 8
Bit 9 = Channel 9

Bit 10 = Channel 10
Bit 11 = Channel 11
Bit 12 = Channel 12
Bit 13 = Channel 13
Bit 14 = Channel 14
Bit 15 = Channel 15

Bit 0 = Channel 0
Bit 1 = Channel 1
Bit 2 = Channel 2
Bit 3 = Channel 3
Bit 4 = Channel 4

15

Figure4.6 Ć Out of RangeStatus Register