2 the "ok" led is off, 2 the ok" led is off – Rockwell Automation Current Input Module User Manual

Page 50

Advertising
background image

5Ć2

DANGER

THIS EQUIPMENT IS AT LINE VOLTAGE WHEN AĆC POWER IS CONNECTED.

DISCONNECT AND LOCK OUT ALL UNGROUNDED CONDUCTORS OF THE AĆC

POWER LINE. FAILURE TO OBSERVE THESE PRECAUTIONS COULD RESULT IN

SEVERE BODILY INJURY OR LOSS OF LIFE.

Turn off power to the module.
If an out of range condition exists, check for an open or

shorted wire between the terminal board assembly and

thetransmitter.
Turn on power to the module.

Step 5.

Verify that the user application program is correct.
For DCS 5000/AutoMax systems, verify that the application

program that references the symbolic names associated

with themodulehas declared thosenames COMMON in

theapplication tasks.
Verify that the symbolic name in question is being

referenced in the application program. This can be done

indirectly by monitoring thesymbolic namewith the

MONITOR function in theReSourceSoftware.
For both DCS 5000/AutoMax and AutoMatesystems,

verify that the program reading the module is executing

fast enough to catch all of the input changes.

Step 6.

Verify that the hardware is working correctly.

DANGER

THIS EQUIPMENT IS AT LINE VOLTAGE WHEN AĆC POWER IS CONNECTED.

DISCONNECT AND LOCK OUT ALL UNGROUNDED CONDUCTORS OF THE AĆC

POWER LINE. FAILURE TO OBSERVE THESE PRECAUTIONS COULD RESULT IN

SEVERE BODILY INJURY OR LOSS OF LIFE.

Verify hardware functionality by systematically swapping

out modules in the rack. Make certain power is off before

removing any module from the rack. After each swap, if

the problem is not corrected, replace the original module

before swapping out the next one.

5.2

The OK" LED is Off

Problem: TheOK" LED on theCurrent Input modulefaceplateis off.

This LED is on when the module passes its powerĆup diagnostics

and is operating properly. The LED is off when the module fails its

powerĆup diagnostics or when a watchdog timeout error occurs. If

the LED remains off after system powerĆup, replace the module as

described in section 3.3.

Advertising