Rockwell Automation Current Input Module User Manual

Page 30

Advertising
background image

4Ć12

If the specified channel has square root extraction enabled and does

not use engineering units, the flow information provided is in the

range of 0 to 4095. The data returned represents the following ratio:

Data

Flow

4095

=

Flow (Maximum)

Set the Maximum Scaling Register (register 24) to 10000 in order to

read the flow information in steps of 0.01%:

Data

Flow

10000

=

Flow (Maximum)

You can also set register 24 to the maximum flow value which will

allow a direct indication of flow.
Bits 8 to 11 are reserved for future use.
Bits 12 to 15, when equal to 0, enable the READYstate, which is the

default condition. When the module is in the READYstate, it is ready

to receive a configuration command.
When bits 12 to 15 are set to a binary value of 1, 2, or 3, their

operations refer to the channel specified in register 23:
D A binary value of 1 (RESET) resets the channel's configuration by

clearing its corresponding data register (registers 0Ć15) and

resetting its bit in the status registers (registers 16Ć21).

D A binary value of 2 (READ) locates the channel's current

configuration information in memory and loads it into registers 24

to 31.

D A binary value of 3 (WRITE) transfers the channel's configuration

information (registers 24 to 31) into the module's memory,

configures the channel, and then sets its bit in the status registers

(registers 16Ć21).

When bits 12 to 15 are set to a binary value of 4 or 5, they reflect the

AĆC power line frequency. The default is 60 Hz.