Rockwell Automation Current Input Module User Manual

Page 28

Advertising
background image

4Ć10

4.1.15

LowAlarm Register (Register 29)

Register 29 defines the Low alarm limit. If a channel's input value is

less than this limit, the channel's correspondingbit in register 18 is

set to one. The value in register 29 is a 15Ćbit signed integer. This

value must be in engineeringunits if scalingis used. If scalingis

used, this value must be smaller than the Maximum ScalingValue

(register 24) and equal to or larger than the Minimum Scaling Value

(register 25). Unscaled data can range from 0 to 4095.
If register 29 does not contain an alarm value less than the High

alarm value, a configuration error will result in register 22. At

powerĆup, the register is set to a default value of 10.

4.1.16

LowLowAlarm Register (Register 30)

Register 30 defines the Low Low alarm limit. If a channel's input value

is less than this limit, the channel's correspondingbit in register 19 is

set to one. The value in register 30 is a 15Ćbit signed integer. This

value must be in engineeringunits if scalingis used. If scalingis

used, this value must be smaller than the Maximum ScalingValue

(register 24) and equal to or larger than the Minimum Scaling Value

(register 25). Unscaled data can range from 0 to 4095.
If register 30 does not contain an alarm value lower than or equal to

the Low alarm value, a configuration error will result in register 22. At

powerĆup, the register is set to a default value of 1.

4.1.17

Configuration Command Register (Register 31)

Register 31 defines what action should be taken if an input value is

out of range, line frequency averaging, the average AĆC line

frequency, and square root extraction. The register also contains the

Configuration Command Code. See figure 4.10.