Rockwell Automation Current Input Module User Manual

Page 37

Advertising
background image

4Ć19

990

!

1000 ! ******************** INITIALIZATION **********************

1010 !

1020 ! Configure the first three channels using the data

&

! statements at 8000.

1030 !

1100 FOR CHANNEL% = 0 TO 2

1110

!

Reset the configuration register

1120

CNF_COMMAND% = 0000H

1130

!

Wait for the config complete flag to be reset

1140

IF CNF_COMP@ = FALSE THEN GOTO 1180

1150

DELAY 10 TICKS

1160

GOTO 1140

1170

!

Specify the channel to be configured

1180

CNF_CHAN_NUM% = CHANNEL%

1190

!

Specify the max scaling, min scaling, highĆhigh, high,

&

!

low, lowĆlow alarm values

1200

READ CNF_MAX%, CNF_MIN%, CNF_AVE_SAMPLE%, CNF_HH_ALARM%,

&

ăăCNF_H_ALARM%, CNF_L_ALARM%, CNF_LL_ALARM%

1210

! Send the WRITE configuration command that specifies

&

! retaining the old value for the out of range mode and

&

! enabling cycle averaging, and disabling square root extraction

&

1230

CNF_COMMAND% = 3000H

1240

!

Wait for the config complete flag to be set

1250

IF CNF_COMP@ = TRUE THEN GOTO 1290

1260

DELAY 10 TICKS

1270

GOTO 1250

1280

!

Check for an error configuring the channel

1290

IF CNF_ERROR@ = TRUE THEN SHUTDOWN@ = TRUE

1300 NEXT CHANNEL%

8000 !

8010 !

ăMax

ĂăMin

Run

High

High

Low

Low

8020 !

Scaling

Scaling

Aver

High

Low

8030 DATA

ă2000,

-100,

20,

1800,

1600,

ă400,

ăă0

8040 DATA

ă3000,

ăăă0,

20,

2500,

2000,

ă500,

ă250

8050 DATA

10000,

ăăă0,

20,

9000,

7500,

2500,

1000

8060 !

9000 !

9010 ! *********************** MAIN LOOP **********************

9990 !

9991 ! If any channels are out of range, then set shutdown flag

9992 !

10000 IF OUT_OF_RANGE% <> 0 THEN SHUTDOWN@ = TRUE

11000 !

11010 ! If tank or startup process or operation process has

&

! high or low alarm, set warning flag

11030 !

11040 IF TANK_H_ALARM@ OR START_H_ALARM@ OR OP_H_ALARM@ OR

&

TANK_L_ALARM@ OR START_L_ALARM@ OR OP_L_ALARM@ THEN & WARNING@ = TRUE

12000 !

12010 ! If tank or startup process or operation process has a

&

! highĆhigh or lowĆlow alarm, set the shutdown flag

12030 !

12040 ĂIF TANK_HH_ALARM@ OR START_HH_ALARM@ OR OP_HH_ALARM@ OR

&

TANK_LL_ALARM@ OR START_LL_ALARM@ OR OP_LL_ALARM@ THEN

&

SHUTDOWN@ = TRUE

13010 !

13020 ! Wait one second then check again

13030 !

13040 DELAY 1 SECONDS

13050 GOTO 10000

Figure 4.12 ĆSample DCS 5000/AutoMax Current Input Application Task