Appendix a, Continued) – Rockwell Automation Current Input Module User Manual

Page 52

Advertising
background image

60 Hz. Line

Freq. Filter

Enabled

Line Freq.

Filters

Disabled

50 Hz. Line

Freq. Filter

Enabled

AĆ2

Appendix A

(Continued)

Input Circuit

D Input Current Range: 4-20 mA
D Resolution: 4

m

A per count (4-20 mA = 0-4095 counts)

D Accuracy: 0.2% across the operating temperature range
D Input Filter: first order, lowpass, 7 Hz breakpoint
D Out of Range Threshold Voltages): below 3.7 mA or above 20.3 mA
D Input Impedance:10M ohms typical at 0 Hz at faceplate connector

ąĂ:250 ohms with Terminal Board

M/NĂ61C549 or 61C550 attached

Noise Rejection

D Line Frequency Filter (Software Selectable): 60 Hz (default) or 50 Hz
D Averaging Filter (Software Selectable): 1 (default) to 60 samples per

average

D Common Mode Rejection: Ć60dB min (averaging filter = 1 and line

filter enabled)

D Normal Mode Rejection: Ć40dB min (averaging filter = 1 and line

filter enabled)

Input Channel Update Times (All times are in milliĆseconds)

Number of

Configured

Channels

Unscaled

Data

Scaled

Data

Square

Root of

Scaled

Data

Running

Average of

Square

Root of

Scaled

Data

One

18.4

18.5

18.7

18.8

Each Added

17.6

17.7

17.9

18

Sixteen

282

283

286

288

One

2.0

2.1

2.3

2.4

Each Added

1.0

1.1

1.3

1.4

Sixteen

17

18.6

21.8

23.4

One

21.6

21.7

21.9

22

Each Added

20.8

20.9

21.0

21.1

Sixteen

333

334

337

339

Advertising