4Ć11

Register 31

Bits 0Ć15

14 13 12 11 10 9

8

7

6

5

4

3

2 1

0

RW RW RW RW

RW RW

RW RW

Bits 1 and 0 = When An Input Value Is Out Of Range, The Current Input Module

Will:

0ă0ă=ăRetain Old Input Value

0ă1ă=ăForce Input Value to Low Low Alarm Value

1ă0ă=ăForce Input Value to High High Alarm Value

1ă1ă=ăRetain Old Input Value

Bits 5 to 2 = Reserved
Bit 6= Cycle Frequency Averaging

ąă

0=ĂEnable

ąă

1=ĂDisable

Bit 7=ĂSquare Root Extraction

ą

0=ĂDisable

ąă

1=ĂEnable

Bits 11 to 8 = Reserved
Bits 15 to 12 = Configuration Command Code

0ă0ă0ă0ă=ĂREADY State

0ă0ă0ă1ă=ĂReset Configuration For This Channel

0ă0ă1ă0ă=ĂRead Configuration For This Channel

0ă0ă1ă1ă=ĂWrite Configuration For This Channel

0ă1ă0ă0ă=Ă50 Hz AĆC Line Frequency

0ă1ă0ă1ă=Ă60 Hz AĆC Line Frequency

- - - -

- - - -

15

Figure 4.10 Ć Configuration Command Register

When configuring a channel, you must define values for registers 23

through 30 before placing a value in register 31. Register 31 must be

the last register that you place a value in as you configure each

channel.
When you are finished with register 31 for the channel you are

configuring, and the module has processed the information, the

module will set bit 15 of register 22 equal to one. You must then set

bits 12 to 15 of register 31 equal to zero. This places the module in

the READY state. The module then resets bit 15 of register 22 which

indicates that it is ready to receive another command. If you attempt

to enter another command before resetting bits 12 to 15 of

register 31, a configuration error will result in register 22.
Bits 0 and 1 specify what action should occur when an input value is

out of range. The default condition is to retain the old input value

from the channel data registers (0 to 15).
Bits 2 to 5 are reserved for future use.
Bit 6 defines whether or not cycle averaging is enabled for the

channel specified in register 23. The default condition (0) enables

cycle averaging.
Bit 7 defines whether or not square root extraction is enabled for the

channel specified in register 23. The default condition (0) disables

square root extraction. The square root function provides flow

information directly from a differential pressure input.