Table 9 - Preventative Maintenance Schedule (11...20 yrs.)

Interval Period (in years from commissioning date)

11

12

13

14

15

16

17

18

19

20

Component
Location

Component
Category

Component/Item

Isolation
Transformer
Cabinet

Air-cooling system

Door Mounted Air Filters

C / R

C / R

C / R

C / R

C / R

C / R

C / R

C / R

C / R

C / R

Top Mounted Main
Cooling Fans

I

I

I

I

RFB/R

I

I

I

I

I

Auxiliary Cooling Fans

I

R

I

I

I

R

I

I

I

R

Integral Magnetics

Isolation Transformer

I

I

I

I

I

I

I

I

I

I

LV Control

Isolation Transformer
Temperature Monitor

I

R

I

I

I

I

I

R

I

I

Voltage Sensing Board

I

I

I

I

I

I

I

I

I

I

Power
Module
Cabinet

Air-cooling system

Door Mounted Air Filters

C / R

C / R

C / R

C / R

C / R

C / R

C / R

C / R

C / R

C / R

Top Mounted Main
Cooling Fans

I

I

I

I

RFB/R

I

I

I

I

I

Power Module

Electrolytic Capacitors

(1)

R

I

I

I

I

I

R

I

I

I

Misc.

HECS

I

I

I

I

I

I

I

I

I

I

LV
Control
Cabinet

Misc.

AC/DC Power Supplies

R

I

I

I

I

I

R

I

I

I

UPS

UPS

I

I

I

I

I

I

I

I

I

I

Batteries (UPS)

(2)

M

R

M

M

R

M

M

R

M

M

LV Control

PLC

I

I

I

I

I

I

I

I

I

I

Control Unit

I

I

I

I

I

I

I

I

I

I

HMI

I

I

I

I

I

I

I

I

I

I

LV Control Relays

I

I

I

I

I

I

I

I

I

I

LV Control Circuit Breakers

I

I

I

I

I

I

I

I

I

I

All

Connections

LV Component Terminal &
Plug-in Connections

I

I

I

I

I

I

I

I

I

I

Medium Voltage Cable
Connections

I

I

I

I

I

I

I

I

I

I

Transformer Secondary
Winding Connections

I

I

I

I

I

I

I

I

I

I

Power Module Input and
Output Power
Connections

I

I

I

I

I

I

I

I

I

I

General

Enhancements

Firmware

Rv

Rv

Rv

Rv

Rv

Rv

Rv

Rv

Rv

Rv

Hardware

Rv

Rv

Rv

Operational
Conditions

Parameters / Variables

I

Rv

I

I

Rv

I

I

Rv

I

I

Spare Parts

Inventory Needs

I

Rv

I

I

Rv

I

I

Rv

I

I

(1) Power Modules are refurbished at factory as part of an exchange program.

(2) Fully discharge and recharge the UPS batteries every 6 months, to extend battery life.