Replace power module – Rockwell Automation 6012DB PowerFlex Medium Voltage Variable Frequency Drive User Manual

Page 91

Advertising
background image

Rockwell Automation Publication 6000-UM001B-EN-P - October 2014

91

Preventative Maintenance and Component Replacement

Chapter 5

Replace Power Module

Table 7 - Power Module Specifications

Fixed-mounted Power Module

1.

Remove the positioning barriers from both sides of the Power Module.

2.

Disconnect the Three-phase Input Power Cables.

Figure 30 - Fixed-mounted Power Module Component Location

Type

Output Rating (Amps)

Dimensions (HxWxD), approx.

Weight, approx.

Fixed-mounted

≤150 A

420 x 180 x 615 mm (16.5 x 7.1 x 24.2 in.)

20 kg (44.1 lb)

151...200 A

420 x 260 x 615 mm (16.5 x 10.2 x 24.2 in.)

25 kg (55.1 lb)

Drawout

201...380 A

575 x 342 x 691 mm (22.6 x 13.5 x 27.2 in.)

40 kg (88.2 lb)

381...420 A

575 x 342 x 910 mm (22.6 x 13.5 x 35.8 in.)

50 kg (110.2 lb)

ATTENTION: Two people are required to handle the Power Modules. Always
handle the drawout Power Modules using the two recessed lifting handles on
both mounting rails (

Figure 33

).

ATTENTION: The high-voltage power source must be switched off before
replacing a Fixed-mounted Power Module. Wait for 20 minutes before opening
the cabinet doors. Verify that all circuits are voltage-free, using a hot stick or
appropriate high voltage-measuring device. Failure to do so may result in injury
or death.

Fuse

Positioning Barriers

Output Copper Bar (not shown)

Connection Location

Fiber Optic Cables Connection Point

Three-phase Input Cables

from Isolation Transformer

Center Jumper Bar