Chapter 5

Preventative Maintenance and Component Replacement

3.

Remove the Output Copper Bars that connect adjacent Power Modules
(

Figure 31

).

If the Power Module is at the end of a row, remove the VSB and Motor
cable instead of an output copper bus.

4.

Disconnect the fiber optic cables.

Figure 31 - Close up of Fiber Optic Location and Power Cables

5.

Carefully withdraw the Power Module.

6.

Install the new Power Module in reverse order of removal.

ATTENTION: When removing the fiber optic cables, be careful to prevent the
cables from straining or crimping as the resulting loss in light transmission will
impact performance.

ATTENTION: Minimum bend radius permitted for the fiber optic cables is 50
mm (2.0 in.). Any bends with a shorter inside radius can permanently damage
the fiber-optic cable.

Motor Cable

VSB Cable

Output Copper Bar

Fiber Optic Cables