Preventative Maintenance and Component Replacement

Power Module Cabinet

Inspect, Clean, or Replace Door Mounted Air Filters

See

Replace/Clean Door Mounted Air Filters on page 81

.

Inspect or Replace Top Mounted Main Cooling Fans

See

Inspect Top Mounted Main Cooling Fans on page 82

.

Inspect Power Modules

1.

Check for damage or degradation of the Power Modules
a. Inspect the power connections for loose connections or any evidence of

discoloration of connections from heating

b. For Drawout Power Module configurations, remove the back plates

from the Power Module Cabinet and inspect the plug-in connectors on
the back of each Power Module. Look for evidence of discoloration
from overheating.

2.

Remove dust or debris from all ventilation openings on the Power Module

3.

Inspect the electrolytic capacitors, located in the ventilation openings of
the Power Module.
a. Inspect for signs of discoloration, odor, or leakage.
b. Replace Power Modules if the capacitors have discoloration, odor, or

leakage.

Inspect, Clean, or Replace Door Mounted Air Filters

90

Inspect or Replace Top Mounted Main Cooling Fans

90

Inspect Power Modules

90

Replace Power Module

91

Install Drawout Power Modules

95

Replace Power Module Fuses

97

Inspect or Replace HECS

99

Inspect or Replace Door Position Limit Switch

100