P443

Upper Limit Of Current Compensation Input Deadband

0

ON

-16384

32767

P444

Lower Limit Of Current Compensation Input Deadband

0

ON

-16384

32767

P445

Proportional Coefficient Of Current Compensation (%)

5

ON

0

199.99

P446

Integral Coefficient Of Current Compensation (ms)

100

ON

0

32767

P447

Lower Limit Of Current Compensation Output

-100

ON

-100

0

P448

Minimum Frequency For Current Compensation

5

ON

0

100

P449

Proportional Coefficient Of Current Compensation
Output (%)

0.99

ON

0

199.99

P450

Upper Limit Of Frequency Compensation Output

100

ON

0

100

P451

Low Speed Voltage Compensation (%)

0.99

OFF

0

10

P452

Low Speed Voltage Compensation Frequency Threshold

20

ON

0

100

P453

V/F Curve
0: Linear
1: Parabolic Curve
2: Predefined Curve #1
3: Predefined Curve #2

1

OFF

0

3

P454

Flux Time (s)

0.5

OFF

0

10

P455

Modulation Index

87.99

ON

0

199.99

P456

Motor Voltage Upper Limit

87.99

ON

0

199.99

P457

Flying Start Voltage Recovery Time (s) (Low Speed
Region)

5

ON

0

163.84

P458

Coefficient A

40

OFF

0

100

P459

Flying Start Voltage Recovery Time (s) (High Speed
Region)

5

ON

0

163.84

P460

Rated Output Frequency

50

OFF

0

75

P461

Restart Enable

0

ON

0

1

P462

Fault Reset Timeout (s)

120

ON

0

120

P463

Flying Start Low/High Speed Regions Boundary (%)

16

ON

0

100

P465

Power Cell Fault Auto Reset Delay (s)

4

ON

0

10

P466

Maximum Output Frequency

50

OFF

0

75

P467

Over Speed Enable

0

OFF

0

1

P470

Version Compatibility Enable

1

OFF

0

1

P497

Major Rev # Of DSP Main Firmware

0

Cannot
Modify

——

——

P498

Minor Rev # Of DSP Main Firmware

2

Cannot
Modify

——

——

P499

Display Fault Masks Button

0

ON

0

1

P500

Display DSP Variables

0

ON

0

1

Parameter
Number

Description

Default
Value

Modify
Root

Lower
Limit

Upper
Limit