Replace power module fuses – Rockwell Automation 6012DB PowerFlex Medium Voltage Variable Frequency Drive User Manual
Page 97

Rockwell Automation Publication 6000-UM001B-EN-P - October 2014
97
Preventative Maintenance and Component Replacement
Chapter 5
Replace Power Module Fuses
Fixed-mounted Power Module
1.
Remove the M8 nut, lock washer, and copper washer from the top and
bottom of the fuse.
2.
Remove the cables from the top and bottom of the fuse, and remove
another copper washer.
3.
Install the new fuse, and replace cables and hardware in reverse order of
removal.
4.
Torque all hardware to specifications (see
).
Figure 34 - Exploded View of Fixed-mounted Power Module Fuse
ATTENTION: Ensure the input circuit breaker feeding the drive is open. Lock out
and tagout the input circuit breaker before performing any work on the drive or
bypass units.
Copper Washer
Lock washer
M8 Nut
Fuse