Preventative Maintenance and Component Replacement

Chapter 5

Replace Power Module Fuses

Fixed-mounted Power Module

1.

Remove the M8 nut, lock washer, and copper washer from the top and
bottom of the fuse.

2.

Remove the cables from the top and bottom of the fuse, and remove
another copper washer.

3.

Install the new fuse, and replace cables and hardware in reverse order of
removal.

4.

Torque all hardware to specifications (see

Torque Requirements on

page 129

).

Figure 34 - Exploded View of Fixed-mounted Power Module Fuse

ATTENTION: Ensure the input circuit breaker feeding the drive is open. Lock out
and tagout the input circuit breaker before performing any work on the drive or
bypass units.

Copper Washer

Lock washer

M8 Nut

Fuse