4 - parameters and function codes, P parameters, Chapter 4 – Rockwell Automation 6012DB PowerFlex Medium Voltage Variable Frequency Drive User Manual

Page 57: Parameters and function codes, Chapter

Advertising
background image

Rockwell Automation Publication 6000-UM001B-EN-P - October 2014

57

Chapter

4

Parameters and Function Codes

P Parameters

Parameter
Number

Description

Default
Value

Modify
Root

Lower
Limit

Upper
Limit

P004

Command Source
0: Communication Port
1: Other Sources

0

OFF

0

1

P005

Restore Factory Settings
40: User Level
30: Setup Level
50: R&D Level

0

OFF

0

50

P007

Number Of Power Cells Per Phase

9

ON

0

9

P008

Motor Rotation Direction Under Local Control
1: Forward
0: Reverse

1

OFF

0

1

P009

Motor Rotation Direction Command Selection:
0: Local
1: DCS

0

OFF

0

1

P010

Power Cell Fault Mask

32767

ON

0

32767

P017

Number Of Motor Pole Pairs

2

OFF

0

100

P018

Enable Flying Start With Encoder

0

OFF

0

1

P019

Encoder Resolution

1024

OFF

0

4096

P020

Mask Bit For System Fault

32767

ON

0

32767

P021

Mask Bit For System Warning

32767

ON

0

32767

P022

Mask Bit For Logic Fault A

32767

ON

0

32767

P023

Mask Bit For Logic Fault B

32767

ON

0

32767

P024

Stop Method
0: Ramp Down
1: Coast Stop

0

ON

0

1

P025

Flux Reduction Enable

0

ON

0

1

P026

Power Angle Threshold For Flux Reduction

0

ON

0

180

P027

Time For Flux Reducing

5000

ON

0

32767

P028

Flux Reduction Ratio

70

ON

0

100

P029

Power Angle Threshold For Flux Restore

0

ON

0

180

P040

Safe Start Condition
0: Zero Frequency Command Required
1: Frequency Command Allowed

1

OFF

0

1

P089

Skip Frequency Enable
0: Disable
1: Enable

0

ON

0

1

Advertising