Replace Top Mounted Main Cooling Fans

The top fan housing consists of a motor and impeller assembly. To replace the
fan, it is necessary to remove the Fan Housing Lid.

1.

Remove and retain four tapping screws around the Fan Housing Lid, and
remove the Lid.

2.

Remove and retain eight M6 x 12 bolts from the Fan Housing Assembly
which connect to the Fan Support Bracket.

ATTENTION: Fan replacement requires working at a significant height from the
floor. Complete this procedure on a safe, stable platform.

ATTENTION: Always perform Power Lockout procedure before servicing
equipment. Verify with a hot stick or appropriate voltage measuring device that
all circuits are voltage free. Failure to do so may result in severe burns, injury, or
death.

M6 x 12 Bolt (4)

Lock washer (4)

Washer (4)

Tapping Screw (4)

M6 x 12 Bolt (8)

Washer (16)

Washer (16)

Lock washer (8)

Fan Housing Lid

Fan Support Bracket

Fan Housing Assembly

Fan Assembly

Wiring Cover

Aviation Plug