Rockwell Automation 6012DB PowerFlex Medium Voltage Variable Frequency Drive User Manual

Page 58

Advertising
background image

58

Rockwell Automation Publication 6000-UM001B-EN-P - October 2014

Chapter 4

Parameters and Function Codes

P090

Skip Frequency 1 Lower Limit

0

ON

0

75

P091

Skip Frequency 1 Upper Limit

0

ON

0

75

P092

Skip Frequency 2 Lower Limit

0

ON

0

75

P093

Skip Frequency 2 Upper Limit

0

ON

0

75

P113

Flying Start-Initial Output Voltage Percentage (%)

5

ON

0

100

P114

Flying Start-Current Comparison Delay For Motor Speed
Search (ms)

1000

ON

0

5000

P115

Flying Start-Current Threshold For Successful Motor
Speed Search

5

ON

0

100

P198

HECS Rated Current (A)

0

ON

0

5000

P199

Motor Rated Current (A)

0

ON

0

5000

P200

Ia Motor Current Memory Address

13

ON

0

500

P201

Motor Ia Scaling Correction Factor

100

ON

0

199.99

P202

Ib Motor Current Memory Address

14

ON

0

500

P203

Motor Ib Scaling Correction Factor

100

ON

0

199.99

P204

Motor Uab Voltage Address

11

ON

0

500

P205

Motor Uab Voltage Scaling Factor Correction

199.99

ON

0

199.99

P206

Motor Uac Voltage Scaling Factor Correction

199.99

ON

0

199.99

P211

Filter Time For Abnormal Output Voltage (ms)

1000

ON

0

32767

P212

Filter Time For Output Short-Circuit (ms)

10

ON

0

32767

P213

Output Short-Circuit Fault Threshold

180

ON

0

199.99

P214

Over Current Low/High Speed Region Boundary

5

ON

0

100

P215

Filter Time For Output Over Current (0.1 s)

200

ON

0

32767

P216

High-Frequency Output Over Current Threshold

120

ON

0

199.99

P217

Low-Frequency Output Over Current Threshold

70

ON

0

199.99

P218

Filter Time For Motor Over Temperature (0.1 s)

6000

ON

0

32767

P219

Motor Over Temperature Warning Threshold

110

ON

0

199.99

P220

Motor Over Temperature Fault Threshold

120

ON

0

199.99

P221

Filter Time For Output Over Voltage (ms)

100

ON

0

32767

P222

Output Over Voltage Fault Threshold

130

ON

0

199.99

P223

Output Voltage Deviation Warning Threshold

60

ON

0

199.99

P224

Output Voltage Deviation Fault Threshold

80

ON

0

199.99

P225

Motor Over Temperature Warning Cancellation
Temperature

100

ON

0

199.99

P226

Output Voltage Abnormality Warning Cancellation
Threshold

50

ON

0

199.99

P227

Ground Fault Detection Scaling Correction Factor

100

ON

0

199.99

P228

Filter Time For Ground Fault (ms)

1000

ON

0

32767

P229

Ground Fault Warning Threshold

20

ON

0

199.99

P230

Ground Fault Trip Threshold

60

ON

0

199.99

P231

Filter Time For Overspeed Fault (Upper Limit)

100

ON

0

32767

Parameter
Number

Description

Default
Value

Modify
Root

Lower
Limit

Upper
Limit

Advertising
This manual is related to the following products: