Rockwell Automation 6012DB PowerFlex Medium Voltage Variable Frequency Drive User Manual

Page 98

Advertising
background image

98

Rockwell Automation Publication 6000-UM001B-EN-P - October 2014

Chapter 5

Preventative Maintenance and Component Replacement

Drawout Power Module

1.

Remove and retain the M12 bolt, washer, lock washer, and nut from the
top and bottom of the fuse.

2.

Remove the fuse from between the fixed bracket and the power cable and
bus bar.

3.

Install the new fuse, and the hardware in reverse order of removal.

4.

Torque all hardware to specifications (see

Torque Requirements on

page 129

).

Figure 35 - Exploded View of Fixed-mounted Power Module Fuse

ATTENTION: Ensure the input circuit breaker feeding the drive is open. Lock out
and tagout the input circuit breaker before performing any work on the drive or
bypass units.

ATTENTION: The hardware connecting the Drawout Power Modules MUST be
reinstalled facing up, as shown in

Figure 35

. Failure to install the hardware in

this manner will affect clearance distance between bolts and can cause an arc.

Washer

Lock washer

M12 x 30 Bolt

Fuse

Washer

Nut

Power Cable

Bus bar

Advertising