Rockwell Automation 6012DB PowerFlex Medium Voltage Variable Frequency Drive User Manual

Page 31

Advertising
background image

Rockwell Automation Publication 6000-UM001B-EN-P - October 2014

31

Drive System Layout

Chapter 2

Figure 21 - Control Unit Layout

Table 2 - Control Unit description

HMI

PWM Board A

DCS

Phase A

Power Modules

Fieldbus

VSB

HECS

PLC

Communication

Board

PWM Board B

PWM Board C

Phase C

Power Modules

DT

AT

DB

CPU Board

Phase B

Power Modules

RJ45 Modbus TCP/IP

RS-485

Modbus

Modbus

Board Function

PWM Board A, B, C

Output PWM and control signals to Power Modules
Collect and process fault and state information from Power Modules to CPU board
Each phase PWM board can control up to nine power cells

CPU Board

Process analog input signals, switch and fault information, control DA and switch signal output,
realize V/F algorithm, set and change parameters in communication with HMI

Analog Signal
Processor Board (AT)

Collect and process analog input signals to CPU Board, output analog signals processed by DT
board

Digital Signal
Processor Board (DT)

Collect and output digital signals, digital to analog conversion function

DB Board

Acts as a base board in the Control Unit and interfaces the digital and analog signal cables

Connector

HMI Communication
Interface

Connection between HMI and Control Unit. Provides inputs from the HMI and PLC to the CPU
Board

Fiber Optic Socket

Connection between Power Modules and Control Unit (two per module)

Interface Terminals

Connects external inputs, outputs and the CPU Board

Status Indicators

Phase control board
transceiver indicator
light

B: board healthy indicator
T: transmit data to power module indicator
R: receive data from power module indicator

CPU Board Indicator Lights

5V

5V power supply indicator

3.3V

3.3V power supply indicator

FPGA

FPGA healthy indicator

DSP1

DSP1 healthy indicator

DSP2

DSP2 healthy indicator