Publication CNET-IN002B-EN-P - June 2010

23

Plan a ControlNet Coax Media System Chapter 2

Tap, Trunk-cable Section, and Terminating Resistors

Select the shortest path for routing the cable to minimize the amount of cable
you need. The specific details of planning such a cable route depends upon the
needs of your network and environments.

There is no minimum trunk-cable section length limit. The maximum
allowable total length of a segment is 1000 m (3280 ft) with two taps
connected. Each additional tap decreases the maximum length of the segment
by 16.3 m (53.4 ft). The maximum number of taps allowed on a segment is 48,
with a maximum length of 250 m (820 ft).

Segment Length and Number of Taps

2

2

3

3

1

1

1

30094-m

Item

Description

1

Tap

2

Terminating resistors

3

Trunk-cable section

1000 (3280)

750 (2460)

500 (1640)

250 (820)

2

16

32

48

Max allowable segment length =
1000 m (3280 ft) - 16.3 m (53.4 ft) X [number of taps - 2]

Number of Taps

S

eg

m

en

t

Le

ng

th

m

(f

t)

30014-m

Allowable
Region