Chapter 3 Install a ControlNet Coax Media System

Install the Trunk Cable

Install your trunk cable, observing your cable supplier’s installation
instructions and these guidelines.

Wire External Enclosures

When you pull the RG-6 type coax cable through multiple conduit bends,
follow these specifications.

Wire Internal Enclosures

When the RG-6 type coax cable is not passed through conduit, follow
these specifications.

For this
coax cable

Pull strength should not exceed Bend radius should not exceed

PVC

42.75 kg (95 lb)

76.2 mm (3.0 in.)

FEP

61.65 kg (137 lb)

69.9 mm (2.75 in.)

Tap drop-cable

42.75 kg (95 lb)

76.2 mm (3.0 in.)

IMPORTANT

DS/3/4 tap drop-cable can be used as trunk cable in a protected
area where space or small

bending radius

is needed. The

maximum length in a segment is limited to 30 m (98.43 ft).

For this coax cable

Bend radius should not exceed

PVC cable

38.1 mm (1.5 in.)

FEP cable

35.6 mm (1.4 in.)

Tap drop-cable

38.1 mm (1.5 in.)